54
7 - CONTROL
Address
Id
Description
U.M.
Note
4264
65 DHW Status Bitmap
Bitmap
Bit
Function
Configuration
0
ON/OFF
0=OFF
1=ON
1
Recirculation
0 = inactive recirculation
1= active recirculation
2
Maintenance
1 = In maintenance
3
DHW with Solar Only
1=DHW with Solar Only
4
DHW with HP
1 = DHW production with HP
5
DHW with Boiler
1 = DHW production with
Bolier
6
DHW with Solar
1 = DHW production with
Solar
7
Anti-legionella
1 = In anti-legionella
8
DHW Pump
0=OFF
1=ON
9
Free
10
Free
11
Free
12
Free
13
Free
14
Free
15
Free
4265
66 Free
4266
67 DHW Setpoint
°C/10
Setpoint
4267
68 Free
4268
69 Free
4269
70 Free
4270
71 Free
4271
72 Free
4272
73 Free
4273
74 Primary flow rate
(l/min)/10
4274
75 Free
4275
76 DHW circuit flow rate
(l/min)/10
Flowmeter (pulses)
4276
77 DHW total consumption
l/10
pulses
4277
78 Free
4278
79 Solar exchanger input probe
°C/10
Temperature probe
4280
81 DHW exchanger intake/circuit temperature sensor °C/10
Temperature probe
Summary of Contents for PAC BT Series
Page 1: ...Installation and operating manual PAC BT 5 kW to 17 kW M0GC6UN16 02 Nov 2016 English version...
Page 2: ......
Page 4: ......
Page 87: ...Airwell Residential AWAU PAC BT UE 5KW H11 AWHK PAC BT UI 5 9KW H11 42 64 3 4 5 XL kW kW kW...
Page 91: ...Airwell Residential 42 64 4 5 7 XL kW kW kW AWAU PAC BT UE 7KW H11 AWHK PAC BT UI 5 9KW H11...
Page 95: ...Airwell Residential 42 64 5 6 8 XL kW kW kW AWAU PAC BT UE 9KW H11 AWHK PAC BT UI 5 9KW H11...
Page 111: ......