33
Reading the objective operating conditions is useful for
checking the unit over time.
With unit of full load, namely in stable conditions and close to
those of work, take the following data:
- Voltage and general absorptions with unit at full load
- Absorption of varied electrical loads (compressors,
fans, pumps etc)
- Temperatures and capacities of different liquid (water,
air) in the inlet and outlet of the unit.
- Temperature and pressures on the characteristic points
of the refrigerating circuit (compressor discharge,
liquid, intake).
The readings should be stored and made available during
maintenance .
6.18 - STARTING REPORT
6 - START-UP
6.16 SYSTEM WATER CLIMATIC CURVES
ESTATE
115
117
INVERNO
Water Reset
Setpoint
T ext
114
112
1
1
6
T ext
113
Set point compensation on outdoor temperature
Summer
With outside low temperatures the refrigerant requirements are
reduced. The indoor comfort can also be obtained with a set-
point higher than standard. The correction is added to the set-
point (increased with the decrease in temperature).
Winter
With outside mild temperatures the thermal requirements are
reduced.
The indoor comfort can also be obtained with a lower set-point.
The correction is subtracted from the set-point (increased with
the decrease in temperature).
Example:
if outside temperature (T. Ext.) > 114, set water = par 52 -117
6.17 - AMBIENT SCHEDULING
The scheduling allows to set the daily time bands and to
allocate the destre operating mode:
Comfort
Economic
Off
Programming
*
↳
Unit programming
↳
Prog S1
Monday
parameter description
Extended description
4
CompExt
Enabling of compensation on ext.
Temp. 0=No ;1=only in Cool; 2=only in
Heat; 3=Always
HP
*
↳
Settings
↳
Parame-
ter
↳
Configuration
par 4
Outdoor T. correction
*
Summer
Winter
Configuration :
parameter description
112
Ext. temp. min. summer correction
113
Outdoor temp. max. summer correction
114
Ext. temp. max. winter correction
115
Ext. temp. min. winter correction
116
Summer correction max. value
117
Winter correction max. value
The unit parameters are overwritten by RCW15 keyboard. Make the customization by using RCW15.
Summary of Contents for PAC BT Series
Page 1: ...Installation and operating manual PAC BT 5 kW to 17 kW M0GC6UN16 02 Nov 2016 English version...
Page 2: ......
Page 4: ......
Page 87: ...Airwell Residential AWAU PAC BT UE 5KW H11 AWHK PAC BT UI 5 9KW H11 42 64 3 4 5 XL kW kW kW...
Page 91: ...Airwell Residential 42 64 4 5 7 XL kW kW kW AWAU PAC BT UE 7KW H11 AWHK PAC BT UI 5 9KW H11...
Page 95: ...Airwell Residential 42 64 5 6 8 XL kW kW kW AWAU PAC BT UE 9KW H11 AWHK PAC BT UI 5 9KW H11...
Page 111: ......