11
2 - INSTALLATION
Outdoor unit
2.1 - CLEARANCES
H1
H
L1
L
W1
W
W2
L2
200 2040 800
800
30
600
100
10
Size
H
L
L2
W1
W
W2
5kW - 9kW
988
450
200
250
942
600
12 kW - 14kW
1234
460
250
300
1087
600
17kW
1137
720
350
350
1738
600
Install
OUTDOOR
in fixed positions
If the unit is installed on a roof or terrace, check the load
capacity and the possibility for discharging the condensate.
Installation standards:
spaces for the air intake/exhaust
condensate water draining
install the unit raised from the ground
Prefer places where the unit doesn't disturb the neighbours.
Avoid installations in places subject to flooding
Avoid installations next to bedrooms or windows.
Avoid snow accumulating obstructing for air ejection and
suction
A correct circulation of the air is indispensible to guarantee the
good working order of the machine.
Avoid therefore:
obstacles to the airflow;
exchange difficulties;
leaves or other foreign bodies that can obstruct the
exchange batteries;
winds that hinder or favour the airflow;
heat or pollution sources close to the unit (chimneys,
extractors etc);
stratification (cold air that stagnates at the bottom);
recirculation (expelled air that is sucked in again);
positioning below the level of the threshold, close to very
high walls, attics or in angles that could give rise to
stratification or recirculation phenomenons.
Ignoring the previous indications could:
energy efficiency decrease;
blocks due to HIGH PRESSURE (in summer) or LOW
PRESSURE (in winter).
Choose the installation place according to the following
criteria:
customer approval
safe accessible position
carry out maintenance operations
technical spaces requested by the unit
water connections
max. distance allowed by the electrical connections
max. distance allowed by the refrigeranting connections
control points with capacity adequate to the unit weight
verify that all bearing points are aligned and leveled
sound levels (TECHNICAL INFORMATION section)
Indoor unit
installed inside
in a dry room/compartment where the temperature cannot
fall below 0 degrees
in fixed positions
Keep to the indicated safety spaces.
Prefer places where the unit doesn't disturb the neighbours.
Avoid installations in places subject to flooding
Avoid installations next to bedrooms or windows.
The spaces can be occupied by objects that must be easily
removeable in case of maintenance interventions.
Summary of Contents for PAC BT Series
Page 1: ...Installation and operating manual PAC BT 5 kW to 17 kW M0GC6UN16 02 Nov 2016 English version...
Page 2: ......
Page 4: ......
Page 87: ...Airwell Residential AWAU PAC BT UE 5KW H11 AWHK PAC BT UI 5 9KW H11 42 64 3 4 5 XL kW kW kW...
Page 91: ...Airwell Residential 42 64 4 5 7 XL kW kW kW AWAU PAC BT UE 7KW H11 AWHK PAC BT UI 5 9KW H11...
Page 95: ...Airwell Residential 42 64 5 6 8 XL kW kW kW AWAU PAC BT UE 9KW H11 AWHK PAC BT UI 5 9KW H11...
Page 111: ......