51
7 - CONTROL
Address
Description
U.M.
Note
2700
Remote mode DHW
Bitmap
Bit
Function
Enable
Note
0
1=ON / 0=OFF
EnComandiRete = 1
ON/OFF via network (1=DHW on; 0=DHW
off) enabled if EnComandiRete=1
1
Free
2
1 = Storage
1 = storage mode via network, enabled if
EnComandiRete=1
3
1 = Recirculation
1 = recirculation mode via network,
enabled if EnComandiRete=1
4
1 = No solar
1 = no solar mode via network, enabled if
EnComandiRete=1
5
1 = Resistances only
1 = DHW heating elements only mode via
network, enabled if EnComandiRete=1
6-15
Free
2701
Setpoint storage
°C/10 Setpoint
EnSetAccumuloRete = 1
Storage tank setpoint set by supervisor
2702
Sanitary Band
°C/10 Temperature
EnBandaSanitariaRete = 1
DHW temperature range setpoint
controlled by supervisor
2703
Maintenace set
°C/10 Setpoint
EnSetMantenimentoRete =1 Maintenance setpoint controlled by
supervisor
2704
Setpoint anti-legionella °C/10 Setpoint
EnSetAntilegioRete = 1
Anti-Legionnaire's disease setpoint
controlled by supervisor
2705
SetHotH20
°C/10 Setpoint
EnSetHotH2ORete =1
DHW maximum temperature setpoint
2706
anti-legionella Timer
min
Time
EnComandoAntilegioRete =1 Interval between anti-Legionnaire's
disease cycles controlled by supervisor
2707
Libero
2708
LowTForceRes
°C/10 Temperature
EnDeltaTForceResRete =1 Minimum DHW temperature to trip safety
heating elements controlled by supervisor
2709
Flag Register DHW
Bitmap
Bit
Function
Configuration
0
EnComandiRete (2700)
EnACSControlRete=1
Remote DHW control enable
1
EnSetAccumuloRete
(2701)
Remote storage tank setpoint enable
2
EnBandaSanitariaRete
(2702)
Remote DHW range enable
3
EnSetMantenimentoRete
(2703)
Remote maintenance setpoint enable
4
EnSetAntilegioRete (2704)
Remote anti-Legionnaire's disease
setpoint enable
5
EnSetHotH2ORete (2705)
Remote DHW maximum temperature
enable
6
EnComandoAntilegioRete
(2706)
Remote anti-Legionnaire's disease interval
enable
7
EnDeltaTForceResRete
(2708)
Remote DHW minimum temperature
heating elements enable
8
EnDeltaTSolareRete
(2711)
Remote solar temperature enable
9-15
Free
2710
Free
2711
DeltaTSolare
°C/10 Temperature
EnDeltaTSolareRete = 1
Remote delta temperature between DHW
and solar to enable solar
DHW controls
Summary of Contents for PAC BT Series
Page 1: ...Installation and operating manual PAC BT 5 kW to 17 kW M0GC6UN16 02 Nov 2016 English version...
Page 2: ......
Page 4: ......
Page 87: ...Airwell Residential AWAU PAC BT UE 5KW H11 AWHK PAC BT UI 5 9KW H11 42 64 3 4 5 XL kW kW kW...
Page 91: ...Airwell Residential 42 64 4 5 7 XL kW kW kW AWAU PAC BT UE 7KW H11 AWHK PAC BT UI 5 9KW H11...
Page 95: ...Airwell Residential 42 64 5 6 8 XL kW kW kW AWAU PAC BT UE 9KW H11 AWHK PAC BT UI 5 9KW H11...
Page 111: ......