7 - CONTROL
Address
Id
Description
U.M.
Note
4239
40 Inverter status (1415)
Bitmap
(inverter)
Bit
Function
Configuration
0
Stop/Run Mode
0=
Stop mode
1=Run Mode
1
Normal/Trip Mode
0=normal mode
1=Trip Mode
2
Stationary state
0= Not stationary
1= Stationary state
3
Acceleration state
0 = no acceleration
1 = acceleration
4
Deceleration state
0 = no deceleration
1 = deceleration
5-11
Reserve
12
Compressor oil return
state
0 = not complete,
1 = Complete
13
Speed of compressor
slowed down by protection
0 = inactive
1 = active
14
Warning, compressor not
connected
0 = Normal,
1 = alarm
15
Reserve
4240
41 Inverter alarms (Trip Type 1416)
Bitmap
Value = 0: Not trip
Value = 1: Heatsink over heat
Value = 2: Over current at acceleration state (Hardware trip)
Value = 3: Over current at steady state (Hardware trip)
Value = 4: Over current at deceleration state (Hardware trip)
Value = 5: DC Bus under voltage
Value = 6: DC Bus over voltage
Value = 7-8: Reserve
Value = 9: PFC Converter over current
Value = 10: Over current at acceleration state (Software trip)
Value = 11: Over load fault
Value = 12: Over current at steady state (Software trip)
Value = 13: Over current at deceleration state (Software trip)
Value = 14: -
Value = 15: Communication loss time out
Value = 16: Heatsink temperature sensor error
Value = 17-19: Reserve
Value = 20: Abnormal condition
Value = 21: PFC Converter fault: Current Limit, Over voltage, Under voltage,
Phase Loss
Value = 22: EEPROM not initialize
4241
42 Inverter Temperature
°C/10
Compressor/Inverter
4242
43 Free
4243
44 Free
4244
45 Free
4245
46 Free
4246
47 Free
4247
48 Free
4248
49 Return temperature
°C/10
Probe temperature
4249
50 Discharge temperature
°C/10
Probe temperature
4250
51 Discharge saturated temperature
°C/10
Thermostatic
4251
52 Operating SuperHeat
°C/10
Thermostatic
4252
53 Regolation valve opening percentage %/10
Thermostatic
4253
54 Overheating current set point
°C/10
Thermostatic
4254
55 Control valve steps
Number
Thermostatic
4255
56 Fixed valve opening percentage
%/10
Thermostatic
4256
57 Fixed valve steps
Number
Thermostatic
Summary of Contents for PAC BT Series
Page 1: ...Installation and operating manual PAC BT 5 kW to 17 kW M0GC6UN16 02 Nov 2016 English version...
Page 2: ......
Page 4: ......
Page 87: ...Airwell Residential AWAU PAC BT UE 5KW H11 AWHK PAC BT UI 5 9KW H11 42 64 3 4 5 XL kW kW kW...
Page 91: ...Airwell Residential 42 64 4 5 7 XL kW kW kW AWAU PAC BT UE 7KW H11 AWHK PAC BT UI 5 9KW H11...
Page 95: ...Airwell Residential 42 64 5 6 8 XL kW kW kW AWAU PAC BT UE 9KW H11 AWHK PAC BT UI 5 9KW H11...
Page 111: ......