31
6.8 - REFRIGERANT CHARGE CHECK
6.9 - DOMESTIC HOT WATER TANK
The unit always leads the DHW to the setpoint p429 value.
During the
storage (A)
phase
the temperature drops until
par 432 (by pwd).
During the
maintenance (M)
phase the temperature drops until
par 431.
It is better to schedule the maintenance phase at night and
during the periods of reduced use of domestic hot water.
If the DHW set point is increased, check that the thermostatic
mixer valve is not set too high.
Example:
If the distance is greater than 5m, add gas and check the
charge.
Proceed as follows to check the charge.
The unit can be in Domestic Hot Water tank mode.
It is important that during the measurements :
- there is enough charge to maintain the unit in
operation
- there are no mode changes (from DHW to the installation
or vice versa)
Turn on the unit
On the multifunction keypad:
Select the required operating mode.
Select required system control
If the water temperature is < 20°C in heating or > 25°C in
cooling, the unit will start late.
Modify the following parameters (by pwd) to allow the unit
operating at the 50% :
396EnManualVcc
= 1
395ManualVcc
= 5,0v
wait at least 15 minutes after unit start up before executing
the readings
NOTE
: the sanitary hot water tap must be opened in
order for the temperature itself in the accumulation to
remain at 30 - 40 °C.
Subcooling calculation :
= temperature read on the high pressure
gauge - temperature detected before the liquid receiver
The correct subcooling is between 1,5 and 2,5 °C
If the values are higher remove gas from the liquid pipe
with unit in operation
If the values are lower add gas, with insufficient charge the
liquid light displays the presence of bubbles.
Wait about 20 minutes to stabilize the unit
Repeat the measure
If necessary add / remove gas
Once reached the optimal charge
Power on/off the unit
6 - START-UP
Scheduling
The scheduling allows to set the daily time bands and to
allocate the destre operating mode :
Ricirculation
Storage
6.10 - ANTI-LEGIONELLA
Enable the function:
Par
435
Enable anti-legionella (1= enable)
Par
436
Antil-egionella set point (password-protected).
*
Programming
↳
Health programming
↳
Prog S1
Monday
HP
*
↳
Settings
↳
Parameters
↳
DHW
p 431
p 432
SET
p 429
A
M
M
A
48°C
45°C
42°C
HP
*
↳
Settings
↳
Parameters
↳
Compressor
Ventilation
HP
*
↳
Settings
↳
Parameters
↳
DHW
The unit parameters are overwritten by RCW15 keyboard. Make the customization by using RCW15.
Summary of Contents for PAC BT Series
Page 1: ...Installation and operating manual PAC BT 5 kW to 17 kW M0GC6UN16 02 Nov 2016 English version...
Page 2: ......
Page 4: ......
Page 87: ...Airwell Residential AWAU PAC BT UE 5KW H11 AWHK PAC BT UI 5 9KW H11 42 64 3 4 5 XL kW kW kW...
Page 91: ...Airwell Residential 42 64 4 5 7 XL kW kW kW AWAU PAC BT UE 7KW H11 AWHK PAC BT UI 5 9KW H11...
Page 95: ...Airwell Residential 42 64 5 6 8 XL kW kW kW AWAU PAC BT UE 9KW H11 AWHK PAC BT UI 5 9KW H11...
Page 111: ......