4.2.10. PRM:9 Servo RMS Current Timeout
This parameter determines how long the current can remain above the RMS threshold
(given in PRM:8) before a fault is generated. Refer to Table 4-11 for parameter settings.
Table 4-11.
Settings for Servo RMS Current Timeout PRM:9
PRM:9
Settings
Default Value
2
Maximum Value
10
Minimum Value
0
Type
Long (32bit)
Units
Seconds
Requires a reset (CTRL-D) before taking effect.
4.2.11. PRM:10 Servo Velocity Trap
This parameter defines the maximum allowable velocity error before a fault occurs. The
absolute value of the velocity error is compared against PRM:10. If it exceeds PRM:10, a
fault occurs. Setting this parameter to zero disables the velocity error check.
If the velocity error exceeds this value, the amplifier will be disabled and it issues a fault.
Refer Table 4-12 for parameter settings.
Table 4-12.
Settings for Servo Velocity Trap PRM:10
PRM:10
Settings
Default Value
0
Maximum Value
65535
Minimum Value
0
Type
Long (32bit)
Units
Counts/Samples
Requires a reset (CTRL-D) before taking effect.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com