1.2. Mechanical Specifications
1.2.1. Mounting and Cooling
Install the drive rack in an IP54 compliant rack mount console to comply with safety standards. Make
sure that there is sufficient clearance for free airflow at the rear and along the sides of the chassis
and for clearance at the rear panel for cables and connections.
External cooling and Fan Tray cooling options require airflow clearance above and below the drive
chassis. Refer to
Section 2.14. Cooling Options [-C0/-C1/-C2 Option]
Table 1-6:
Mounting Specifications
iXR3/XR3
Customer-Supplied Enclosure
IP54 Compliant
Weight
~25 kg
Dimensions
Refer to
Minimum Clearance
Airflow
~25 mm
Connectors
~100 mm
Operating Temperature
Refer to
Section 1.3. Environmental Specifications
WARNING
:
Heavy Object
1. Use a cart to move the product.
2. To avoid injury, use two or more people to move and install this product.
3. Lift this product only by the base. Do not use the cables or the connectors to lift or
move this product.
4. Do not use the handles on the front of the product to lift or move this product. Use
the handles only to slide the product in and out of its enclosure.
iXR3/XR3 Hardware Manual
1.2. Mechanical Specifications
www.aerotech.com
25
Summary of Contents for Automation1 iXR3
Page 1: ...Revision 2 08 Automation1 iXR3 and XR3 Drive Racks HARDWARE MANUAL...
Page 97: ...Figure 3 3 Slot Details iXR3 XR3 Hardware Manual 3 3 Amplifier Replacement www aerotech com 97...
Page 111: ...W Warranty and Field Service 99 iXR3 XR3 Hardware Manual Index www aerotech com 111...
Page 112: ...Index iXR3 XR3 Hardware Manual This page intentionally left blank 112 www aerotech com...