Table 10-2: Outdoor Reset Preset Selections
Preset
Minimum Setpoint
Maximum Setpoint
Low Mass Radiant
80ºF [27ºC]
140ºF [60ºC]
High Mass Radiant
80ºF [27ºC]
120ºF [49ºC]
Cast Iron Baseboard
100ºF [38ºC]
170ºF [77ºC]
Finned Tube Baseboard
120ºF [49ºC]
180ºF [82ºC]
Radiators
120ºF [49ºC]
170ºF [77ºC]
Fan Coil
140ºF [60ºC]
180ºF [82ºC]
10.7.6 Set Warm Weather Shutdown Temperature (Default: OFF)
Warm Weather Shutdown prompts the installer to enter an optional outdoor temperature at which
to disable the central heating function. The Esteem will continue to respond to a domestic hot
water call or a 0-10VModulation Signal when the outdoor temperature exceeds the Warm
Weather Shutdown Temperature setting. Press the LEFT or RIGHT buttons to adjust the Warm
Weather Shutdown Temperature then press the OK button to store the setting. The Warm
Weather Shutdown icon (
) is displayed on the home screen when the outdoor temperature
reaches the Warm Weather Shutdown Temperature.
Figure 10-9: Set Warm Weather Shutdown Temperature Menu