18.3.13 CH Post Pump Time (Default: 1 Minute)
Figure 18-17: CH POST PUMP TIME Menu
CH Post Pump Time sets how long the central heating circulators will continue to operate at the
completion of a heating call. Reference System Pump in CH Settings in section 18.3 to
determine which circulators will continue to operate. Any call during the CH Post Pump Time will
be ignored until the post pump has completed. The CH Post Pump feature allows the heat
remaining in the boiler at the completion of a call to be sent to the heating system, which will
improve the overall efficiency of the system. Press the LEFT or RIGHT buttons to adjust the CH
Post Pump Time then press the OK button to store the setting.
=======================================================================