18.9 CASCADE INFORMATION
MENU
Navigation: Home Screen > Installer Menu > Cascade > Cascade Information
INSTALLER Menu Cascade Menu Cascade Information Menu
Figure 18-53: Cascade Information Menu Navigation
Cascade Information provides real time operating information of the Cascade System. Each line
contains an information item followed by its current value. See below for a list of all Cascade
Information items.
18.9.1 System Temperature Logging
The System Temperature selection in the Cascade
Information Menu displays a logging function which
records one sample every 12 minutes to produce a
graph of the last 24 hours. Select System
Temperature in Cascade Information then press the
oK button to view the graph.
Table 18-7: Cascade Information Menu Items
Menu Item
Description
Cascade Role
Displays the current role of the boiler in the Cascade System. Cascade
Role will be one of the following:
•
Master:
Indicates this boiler is the Master boiler in the Cascade
System.
•
Slave:
Indicates this boiler is a Slave boiler in the Cascade
System.
•
Standalone:
Indicates this boiler is not part of a Cascade System.
System Temperature
Displays the current system temperature reading wired to the Master
boiler. If the system sensor is not wired in to the Master boiler,”--” is
displayed.
Active Boilers
Displays the current number of boilers fired in the Cascade System.
Total Boilers
Displays the total number of boilers in the Cascade System.
Cascade Firing Rate
Displays the current firing rate of the entire Cascade System.
Figure 18-54: System Temperature
Logging Display