18.5 BOILER SETTINGS MENU
Navigation: Home Screen > Installer Menu > CH & DHW Settings > Boiler Settings
INSTALLER Menu CH & DHW SETTINGS Menu BOILER SETTINGS Menu
Figure 18-39: Navigation to the BOILER SETTINGS Menu
The Boiler Settings menu contains settings related to general boiler operation. Each line contains a Boiler
Setting followed by its current value.
========================================================================
18.5.1 Lockout Temp (Default: 210°F [99°C])
Lockout Temp. allows the High Boiler Temperature lockout (E3) to be temporarily adjusted down
to 102°F [39°C] for inspector demonstration. Press the UP or DOWN buttons to select 210°F
[99°C] or 102°F [39°C], then press the OK button to store the setting.
Figure 18-40: LOCKOUT TEMP. Menu
•
102°F [39°C]:
A High Boiler Temperature lockout (E3) will occur when the boiler temperature
reaches 102°F [39°C].
•
210°F [99°C]:
A High Boiler Temperature lockout (E3) will occur when the boiler temperature
reaches 210°F [99°C].