Command Set
•
59
3.21 Read enable/disable CJC Status
@Description
To read CJC disable/enable status of ND-6018
@Syntax
$(Addr)D<CR>
$
Command leading code
(1 character)
(Addr)
Address ID
(2 character)
D
Read CJC disable/enable staus command
(1
character)
@Response
!(Addr)(Statu
s)<CR>
or
?(Addr)<CR
>
!
Command is valid.
?
Command is invalid.
(Stat
us)
0: Disable
1: Enable
@Example
User
command:
$02D<CR>
Response:
!021<CR>
To read CJC disable/enable status, and module’s address is 02H., the
CJC is enable.
(6011/D, 6018)
Summary of Contents for NuDAM-6017