78
•
Command Set
3.38 Set Low Alarm
@Description
Set low alarm limit value at specified analog input module.
@Syntax
@(Addr)LO(Data)<CR>
@
Command leading code
(Addr)
Address ID
LO
Set low alarm limit value.
(Data)
Alarm low limit value.
Data format is engineering units. (an + or - sign with
five decimal digits and a decimal fixed point.
@Response
!(Addr)<CR>
!
Command is valid.
(Addr)
Address ID.
@Example
User command:
@06LO+100.00<CR>
Response:
!06<CR>
Set low alarm limit value to +100
°
C to accept J-type thermocouple input
at address 06H.
(6011/D, 6012/D, 6014D)
Summary of Contents for NuDAM-6017
Page 2: ......