16
3
Temp B
Thyrist temp warning
64
9
P2 / 0
P2 / Output actual power
* 125 = Pn (acc CCR size)
* digit = Pn / 125
* eg 24W / 3kVA CCR
* resol = 0,8%
* Lsb= P2 / 0
17
VA-A
VA-drop level A
65
P2 / 1
18
VA-B
VA-drop level B
66
P2 / 2
19
Cf
Current fault
67
P2 / 3
20
LF A
Lamp fault alarm
68
P2 / 4
21
LF B
Lamp fault warning
69
P2 / 5
22
EF A
Earth fault alarm ( trip / m)
70
P2 / 6
23
EF B
Earth fault warning
71
P2 / 7
24
4
EF maint on
EF mainten. Switch on
72
10
Circ 5
Circuit 5 selected
25
EF / 0
EF / Earth fault value
* value 0-100
* 127=off
* Max 50M or 1G
* Lsb= EF / 0
73
Circ 6
Circuit 6 selected
26
EF / 1
74
SCO
Series Cutout Open (Option)
27
EF / 2
75 - 79
Reserved
28
EF / 3
80-82
11
Type
0=Norm,1=Dir,2-6=Cs2-6
29
EF / 4
83
Reserved
30
EF / 5
84-87
Size
1=2,5kVA, 2=3kVA, 3=4kVA…12=30kVA
31
EF / 6
88
12
On a
Feedback of the other serial interface control bits
when redundant duplicate interface is used
32
5
EF scale 0
Earth fault value scale
0=1k, 1=10k, 2=100k or 10M
89
On b
33
EF scale 1
90
On c
34
LF / 0
LF / Qty of lamp faults
* 0-62 lamp faults
* 63= monitoring off
* Lsb = LF / 0
91
Dir2 / C 1
35
LF / 1
92
Circ 2
36
LF / 2
93
Circ 3
37
LF / 3
94
Circ 4
38
LF / 4
95
Hb.
39
LF / 5
96-104 13
Reserved
40-47 6
Reserved
105-112 14
Reserved
113-120 15
Reserved
121-128 16
Reserved
(1) Fast I2: fast over current detection
(2) SCO: Optional series cut out device which opens the circuit for safe maintenance works.
Detailed descriptions of the numeric values
EF (earth fault) isolation resistance / Bytes 4, 5
The isolation resistance value has two scaling bits: code 0= 1k / 1=10k and 2=100k or 10M ohms (in byte 5) to reduce the bits required to
indicate the large scale of 1kohm-50Mohm and 1kohm-1Gohm respectively with proper accuracy. The value (0-100) has 7 bits (byte 4) and
the display value can be calculated by multiplying it with the scale factor.
Value 127 means that the monitoring function is off ( Local control switch off )
No of lamp faults LF / Byte 5
No of lamps faults (0-62) is coded with 6 bits in byte 5.
Value 63 indicates that the LF-monitor is off (CCR off / not all circuits selected)
I2 output current / Byte 7
The range is always from 0 to 8A regardless of the CCR size (CCR nominal output current is 6,6A). Value 160 is 8A and zero 0A.One digit is
therefore 8A/160 =0,05A the resolution being 0.6%. Full range is used in order to display possible overshoots of nominal range, to get
round numbers on PC display and also to minimize (often actions on change based) data transmission between the data collecting PLC and
the monitoring PC which is displaying the values.
IDM 8000
Appendix D – Serial control interface signal list – Modbus TCP
74
Copyright
©
ADB Safegate, All Rights Reserved
Summary of Contents for IDM 8000
Page 1: ...IDM 8000 CCR User Manual UM_IDM 8000 Rev 1 7 2021 05 06 ...
Page 2: ......
Page 8: ...IDM 8000 TABLE OF CONTENTS viii Copyright ADB Safegate All Rights Reserved ...
Page 10: ...IDM 8000 List of Figures x Copyright ADB Safegate All Rights Reserved ...
Page 12: ...IDM 8000 List of Tables xii Copyright ADB Safegate All Rights Reserved ...
Page 18: ...IDM 8000 Safety 6 Copyright ADB Safegate All Rights Reserved ...
Page 20: ...IDM 8000 About this Manual 8 Copyright ADB Safegate All Rights Reserved ...
Page 76: ...IDM 8000 Troubleshooting 64 Copyright ADB Safegate All Rights Reserved ...
Page 104: ...IDM 8000 Appendix J Spare part list 92 Copyright ADB Safegate All Rights Reserved ...
Page 106: ...IDM 8000 Appendix K Components of electronics 94 Copyright ADB Safegate All Rights Reserved ...
Page 113: ...UM_IDM 8000 Rev 1 7 2021 05 06 101 Copyright ADB Safegate All Rights Reserved ...
Page 114: ...IDM 8000 Appendix M Output Terminals 102 Copyright ADB Safegate All Rights Reserved ...
Page 118: ......