Note
: CCR can only start-up between ±15% of U1nom. After start-up it will operate between A- and A+ (-20%...+15%). If the
CCR is not in operation (Off state), Input voltage alarm A is given from –15% level.
B-levels are used as warning indication and can be set by the user. Reset mode is always A (resets automatically when actual
value returns within acceptable limits).
Header / function
Data 1
Data 2
Fact set
Allowed range
Input voltage protection
Nominal value
Nom
Project *
HW setting w.dip switch
Threshold level B +
L b, +
Project *
Lb- … L a + in 1V steps **
Threshold level B –
L b, -
Project *
La- … - Lb + in 1V steps
Delay time
Delay
1s
0.1-10s in 0.1s steps
* Factory settings vary according the nominal input voltage of the project.
** L a, + and L a, - automatically set from the nominal value.
Setting sequence
1. Go to input voltage protection by selecting Set / Prot /U1.
1. Nominal value is displayed, select Next.
1. If necessary adjust levels Lb + and Lb – with + - , select Set and then select Next.
1. If necessary adjust delay time as in step 3.
Operational test
Change the U1 calibration in order to go beyond threshold limits (L a +/- or L b +/-) and make sure that the required function operates in
due time.
4.5.5 Input Frequency and Temperature Protection
Frequency function protects the lamps in the AFL circuit and also the CCR from possible regulation/component fault of the
CCR caused by long term input frequency fault.
If the input frequency is out of acceptable limits (F a, + and F a, -, automatically derived from nominal value) for a predefined
delay time the CCR trips. CCR can start automatically when the input frequency returns within acceptable limits.
Function
Limit type
Fnom
Trip level
Return level
Input frequency protection
Threshold level A +
50/60Hz
Fnom +10% (55/66Hz)
Fnom + 7.5% (54/65Hz)
Threshold level A –
50/60Hz
Fnom –10% (45/54Hz)
Fnom – 7.5% (46/55Hz)
UM_IDM-8000, Rev. 1.7, 2021/05/06
35
Copyright
©
ADB Safegate, All Rights Reserved
Summary of Contents for IDM 8000
Page 1: ...IDM 8000 CCR User Manual UM_IDM 8000 Rev 1 7 2021 05 06 ...
Page 2: ......
Page 8: ...IDM 8000 TABLE OF CONTENTS viii Copyright ADB Safegate All Rights Reserved ...
Page 10: ...IDM 8000 List of Figures x Copyright ADB Safegate All Rights Reserved ...
Page 12: ...IDM 8000 List of Tables xii Copyright ADB Safegate All Rights Reserved ...
Page 18: ...IDM 8000 Safety 6 Copyright ADB Safegate All Rights Reserved ...
Page 20: ...IDM 8000 About this Manual 8 Copyright ADB Safegate All Rights Reserved ...
Page 76: ...IDM 8000 Troubleshooting 64 Copyright ADB Safegate All Rights Reserved ...
Page 104: ...IDM 8000 Appendix J Spare part list 92 Copyright ADB Safegate All Rights Reserved ...
Page 106: ...IDM 8000 Appendix K Components of electronics 94 Copyright ADB Safegate All Rights Reserved ...
Page 113: ...UM_IDM 8000 Rev 1 7 2021 05 06 101 Copyright ADB Safegate All Rights Reserved ...
Page 114: ...IDM 8000 Appendix M Output Terminals 102 Copyright ADB Safegate All Rights Reserved ...
Page 118: ......