U1 calibration
1. Connect external calibrated V-meter (appropriate scale, accuracy better than 1%) to the CCR mains input terminals (main switch).
Warning!
Line voltage circuit – use appropriate test probes!
1. Go to /U1 calibration: select Set/Cal/ In.
1. Adjust the U1 reading on data 1 to equal with the external meter reading.
1. Make sure that the readings are equal then select Set.
1. Check View/In that both readings are equal, if necessary repeat steps 3-5.
Note : Calibration for DC1 (+5V), DC2 (+12V) and DC3 (-12V) system voltages also provided in this display. Factory settings: not necessary to
calibrate during commissioning.
4.4.3 Lamp Fault and VA-Drop Calibration
Header / function
Data 1
Data 2
Remarks
Lamp fault cal
I2 / A (Fact set 2,80A)
Lflim
+ - adjust, Set, Next
Measured LF voltage
Lfcal = 0
Run steps 1-7 and set, Next
Qty of real lamp faults
Lfcal > 0
+ - adj. Run 1-7,Set
Lamp Fault and VA-drop calibration
1. Make sure that there are no lamp faults in the circuit.
Note : All isolation transformers must be of the same size and make in order to
achieve the full accuracy of the lamp fault monitoring function.
1. Go to lamp fault calibration, select Set/Cal/Lf.
1. If necessary adjust Lflim value (factory setting 2.80A for typical trafos) then select Next.
1. Start the CCR and control from Datafield 1 the measurement value to be below 0.8 on all steps. To adjust the value, change the Lflim
value between 1.75A and 3.50A, re-check the measurement value. To calibrate, start the CCR with step 1, wait 30 seconds and select Set.
Note : For circuit selector CCRs ensure that all circuits are selected. Lamp fault monitoring function will only activate when all circuits are
selected.
1. Increase the brilliancy step, wait 30 s and select Set. Repeat this until step 7 is set.
Note : VA-drop full load values are automatically
calibrated at the same time.
Warning!
High voltage circuit - De-energize CCR before working with the load
circuit!
1. Arrange desired amount of real lamp faults to the circuit.
Note : Use either level A amount of lamp faults or not less than 2 or more than
7 is required.
Warning!
High voltage circuit – De-energize CCR before working with the load
circuit!
UM_IDM-8000, Rev. 1.7, 2021/05/06
29
Copyright
©
ADB Safegate, All Rights Reserved
Summary of Contents for IDM 8000
Page 1: ...IDM 8000 CCR User Manual UM_IDM 8000 Rev 1 7 2021 05 06 ...
Page 2: ......
Page 8: ...IDM 8000 TABLE OF CONTENTS viii Copyright ADB Safegate All Rights Reserved ...
Page 10: ...IDM 8000 List of Figures x Copyright ADB Safegate All Rights Reserved ...
Page 12: ...IDM 8000 List of Tables xii Copyright ADB Safegate All Rights Reserved ...
Page 18: ...IDM 8000 Safety 6 Copyright ADB Safegate All Rights Reserved ...
Page 20: ...IDM 8000 About this Manual 8 Copyright ADB Safegate All Rights Reserved ...
Page 76: ...IDM 8000 Troubleshooting 64 Copyright ADB Safegate All Rights Reserved ...
Page 104: ...IDM 8000 Appendix J Spare part list 92 Copyright ADB Safegate All Rights Reserved ...
Page 106: ...IDM 8000 Appendix K Components of electronics 94 Copyright ADB Safegate All Rights Reserved ...
Page 113: ...UM_IDM 8000 Rev 1 7 2021 05 06 101 Copyright ADB Safegate All Rights Reserved ...
Page 114: ...IDM 8000 Appendix M Output Terminals 102 Copyright ADB Safegate All Rights Reserved ...
Page 118: ......