IP482 Industrial I/O Pack User’s Manual Counter Timer Module
___________________________________________________________________
________________________________________________________________________________________
Acromag, Inc. Tel:248-295-0310 Fax:248-624-9234 Email:[email protected] http://www.acromag.com
53
Type:
Flat Ribbon Cable, 50-wires (female connectors at both ends). The
‘-x’ suffix designates the length in feet (12 feet maximum). Choose
shielded cable according to model number. The shielded cable is highly
recommended for optimum performance with analog input or output
modules.
Application:
Used to connect a Model 5025-552 termination panel to the
AVME9630/9660 or APC8620/1 non-intelligent carrier board connectors
(both have 50-pin connectors).
Length:
Last field of part number designates length in feet (user-specified,
12 feet maximum). It is recommended that this length be kept to a
minimum to reduce noise and power loss.
Cable:
50-wire flat ribbon cable, 28 gage. Shielded cable model uses
Acromag Part 2002-261 (3M Type 3476/50 or equivalent).
Headers (Both Ends):
50-pin female header with strain relief.
Header -
Acromag Part 1004-512 (3M Type 3425-6600 or equivalent).
Strain
Relief -
Acromag Part 1004-534 (3M Type 3448-3050 or equivalent).
Keying:
Headers at both ends have polarizing key to prevent improper
installation.
Schematic and Physical Attributes:
See Drawing 4501-463.
Shipping Weight:
1.0 pound (0.5Kg) packaged.
Type:
Termination Panel For AVME9630/9660 or APC8620 Boards
Application: To connect field I/O signals to the Industrial I/O Pack (IP).
Termination Panel:
Acromag Part 4001-040 (Phoenix Contact Type
FLKM 50). The 5025-552 termination panel facilitates the connection of
up to 50 field I/O signals and connects to the AVME9630/9660 3U/6U or
APC8620/1 non-intelligent carrier boards (field connectors only) via a flat
ribbon cable (Model 5025-551-x). The A-D connectors on the carrier
board connect the field I/O signals to the P2 connector on each of the
Industrial I/O Pack modules. Field signals are accessed via screw
terminal strips. The terminal strip markings on the termination panel (1-
50) correspond to P2 (pins 1-50) on the Industrial I/O Pack (IP). Each
Industrial I/O Pack (IP) has its own unique P2 pin assignments. Refer to
the IP module manual for correct wiring connections to the termination
panel.
Schematic and Physical Attributes:
See Drawing 4501-464.
Field Wiring:
50-position terminal blocks with screw clamps. Wire range
12 to 26 AWG.
Connections to AVME9630/9660 or APC8620/1:
P1, 50-pin male header
with strain relief ejectors. Use Acromag 5025-551-x cable to connect
panel to VME board. Keep cable as short as possible to reduce noise
and power loss.
Mounting:
Termination panel is snapped on the DIN mounting rail.
APPENDIX
CABLE: MODEL 5025-
551-x (Shielded)
TERMINATION PANEL:
MODEL 5025-552