79
˙
The electronic thermal overload function is depended on the motor overload protection start current (ie.
Motor rated current). The setting range is 10~120% of inverter rated current. The standard set value for
each capacity has already set at factory as following. If the general-purpose motor rated current value is
different from the standard value, change the setting.
˙
220V Class Common in 3-phase and Single-phase Series
3-phase
JNTABDCB JK---
Model
Single-phase
JNTBBDCB JK---
R500 0001 0002 0003 0005 7R50
0010
Max. Applicable HP
Motor Capacity (KW)
0.5
(0.4)
1
(0.75)
2
(1.5)
3
(2.2)
5
(3.7)
7.5
(5.5)
10
(7.5)
Motor Current Value at
Factory Setting (A)
2.1 3.3 6.4 8.6 13.5
20.1
25.1
˙
440V Class 3-phase Series
Model
JNTABDCB
AZ----
R500 0001
0002
0003
0005
7R50
0010
Electronic thermal
characteristics
0 For
standard
motor
1
For constant torque motor
Electronic thermal time
constant
0
For standard motor and
constant torque motor
1
For motor other than listed in 0
above.
(Short time rating)