68
Function
Pn-
Name
Description
Initial
Setting
User
Set
Values
Ref.
Par.
34
Multifunction
Output
Selection 1
(Terminal 13
Function
Selection)
0:Running
1:Frequency agreement
2:Zero speed
3:Frequency detection (output
frequency
≧
frequency detection
level)
4:Overtorque detection
0
Photo
Coupler
Output
Signal
35
Multifunction
Output
Selection 2
(Terminal 14
Function
Selection)
0:Running
1:Frequency agreement
2:Zero speed
3:Frequency detection (output
frequency
≧
frequency detection
level)
4:Overtorque detection
1
2.7.16
2.7.17
Desired
Speed
Detection
36
Frequency
Detection
Level
Setting unit:0.1 Hz,
Setting range:0.0 to 400.0Hz
0.0Hz
2.7.17
4 3 2 1
- - - 0
Overtorque detection
not provided
- - - 1 Overtorque
detection
provided
- - 0 - Detected
only
frequency
agreement
- - 1 - Detected
during
running
- 0 - - Operation
continues
after overtorque
- 1 - - detection
output
shut-off
at overtorque detection
0 - - -
37
Overtorque
Detection
Function
Selection
1 - - -
Not used
0000
38
Overtorque
Detection
Level
Setting unit:1%,
Setting range: 30 to 200% of inverter
rated current
160%
Over-
torque
Detection
39
Overtorque
Detection
time
Setting unit:0.1s,
Setting range:0.1 to 10.0s
0.1s
2.7.18