75
2.7.4
ACCEL / DECEL TIME SETTING
Item Name
Constant to be set
Factory Preset
Acceleration Time 1
9
10.0s
Deceleration Time 1
10
10.0s
Acceleration Time 2
11
10.0s
Deceleration Time 2
12
10.0s
Accel/Decel Time Select
32 , 33
See page 63.
˙
Each item can be set from 0.0 sec to 600 sec.
The set time indicates the interval required before the maximum output freqnency setting Pn-02 is
reached.
Accel/decel time can be set for two-step switching using multifunction contact input (control circuit
terminals 4 or 5 ), even during running.
Between control circuit terminals 4 or 5.
˙
open : Pn-09 and Pn-10 are selected.
˙
closed : Pn-11 and Pn-12 are selected
(When setting = 6 )
Output Frequency
Pn-11
Pn-12