59
(1mA) full-scale, 3V full-scale output is used at
maximum output frequency [constant (Pn-02)]
operation.Set constant (Pn-45)=0.30.
Description
Key Operation
Digital Operator Display
Remarks
z
Frequency reference value is displayed.
z
Select PRGM mode.
z
Select constant (Pn-45 )
z
Display Pn-45 data.
z
Change the set value
z
Write in the set value. (“End is displayed)
The data are displayed
LED DRIVE OFF
(Note)
Displayed for 0.5 second.
Confirm the display.
Note:
1.
Since analog monitor gain is set to 1.00 prior shipping, 10V is output at maximum output frequency
[constant (Pn-02)] operation.
2.
By data display of constant (Pn-45) in the program mode, voltage at 100% level according to the
constant (Pn-45) set value is output by the meter calibrating function without any conditions.
(Example) Assuming constant(Pn-45)=0.30 : 10V
×
0.30=3V is output without any conditions.
RESET
DATA
STR
DRIVE
PRGM
DATA
STR
Pn-01
Pn-45
0.30
1.00
0.30
DSPL