206
AXM-IO22
Address
Parameter
Default
Range
Data type
Property
10b5H
DI21~24 type
0
Bit0: DI21, Bit1: DI22,
Bit2: DI23, Bit3: DI24
0: DI, 1: pulse counter
word
R/W
10b6H
DI pulse constant
0
1~65535
word
R/W
10b7H
Wo r k i n g m o d e o f
DO3,4
0
0: pulse output,
1: alarming output
word
R/W
10b8H
DO Pulse width
20
20~1000ms
word
R/W
10b9H
DO3 output
0
0: none
1: consumption power
2: gererating power
3: absorption reactive
power
4: generating reactive
power
word
R/W
10baH
DO4 output
0
Same as above
word
R/W
10bbH
AO3,4 type
1 or 2
0: 0~20mA, 1: 4~20mA,
2: 0~5V, 3: 1~5V
word
R/W
AXM-IO32
Address
Parameter
Default
Range
Data type
Property
10bcH
DI25~28 type
0
Bit0: DI25, Bit1: DI26,
Bit2: DI27, Bit3: DI28
0: DI, 1: pulse counter
word
R/W
10bdH
DI pulse constant
0
1~65535
word
R/W
10beH
Working mode of relay
7 and 8
0
0: control output,
1: alarming output
word
R/W
10bfH
Output mode of relay
7 and 8
0
0: latch, 1: pulse
word
R/W
10c0H
Pulse width
50
50~3000
word
R/W
10c1H
AI3,4 type
1 or 2
0: 0~20mA, 1: 4~20mA,
2: 0~5V, 3: 1~5V
word
R/W
AO transforming select
Shop for Power Metering products online at:
1.877.766.5412
www.
PowerMeterStore
.com
Summary of Contents for Acuvim II
Page 2: ...Shop for Power Metering products online at 1 877 766 5412 www PowerMeterStore com...
Page 8: ...VI Shop for Power Metering products online at 1 877 766 5412 www PowerMeterStore com...
Page 16: ...8 Shop for Power Metering products online at 1 877 766 5412 www PowerMeterStore com...
Page 55: ...47 Shop for Power Metering products online at 1 877 766 5412 www PowerMeterStore com...
Page 60: ...52 Shop for Power Metering products online at 1 877 766 5412 www PowerMeterStore com...
Page 167: ...159 Fig 5 46 Shop for Power Metering products online at 1 877 766 5412 www PowerMeterStore com...
Page 268: ...260 Shop for Power Metering products online at 1 877 766 5412 www PowerMeterStore com...