6.3.5 I/O Modules Settings
I/O module setting changes will be made only if the corresponding I/O modules
are installed, no changes will be made otherwise. Please check the I/O module
connection status before doing any settings. Function code: 03H for reading,
10H for writing. Please refer to Chapter 5 Extended Modules for more details.
AXM-IO11
Address
Parameter
Default
Range
Data type Property
109eH DI1~6 type
0
Bit0: DI1, Bit1: DI2
Bit2: DI3, Bit3: DI4
Bit4: DI5, Bit5: DI6
0: DI,1: pulse counter
word
R/W
109fH
DI pulse constant
0
1~65535
word
R/W
10a0H
Working mode of relay 1
and 2
0
0: control output,
1: alarming output
word
R/W
10a1H
Output mode of relay 1
and 2
0
0: latch, 1: pulse
word
R/W
10a2H Pulse width
50
50~3000ms
word
R/W
AXM-IO21
Address
Parameter
Default
Range
Data type Property
10a3H DI7~10 type
0
Bit0: DI7, Bit1: DI8
Bit2: DI9, Bit3: DI10
0: DI,1: pulse counter
word
R/W
10a4H DI pulse constant
0
1~65535
word
R/W
10a5H Working mode of DO
0
0: pulse output
1: alarming output
word
R/W
10a6H DO pulse width
20
20~1000ms
word
R/W
Shop for Power Metering products online at:
1.877.766.5412
www.
PowerMeterStore
.com
Summary of Contents for Acuvim II
Page 2: ...Shop for Power Metering products online at 1 877 766 5412 www PowerMeterStore com...
Page 8: ...VI Shop for Power Metering products online at 1 877 766 5412 www PowerMeterStore com...
Page 16: ...8 Shop for Power Metering products online at 1 877 766 5412 www PowerMeterStore com...
Page 55: ...47 Shop for Power Metering products online at 1 877 766 5412 www PowerMeterStore com...
Page 60: ...52 Shop for Power Metering products online at 1 877 766 5412 www PowerMeterStore com...
Page 167: ...159 Fig 5 46 Shop for Power Metering products online at 1 877 766 5412 www PowerMeterStore com...
Page 268: ...260 Shop for Power Metering products online at 1 877 766 5412 www PowerMeterStore com...