177
The digital inputs in the response message are packed as one input per bit of
the data field. Status is indicated as 1=ON; 0=OFF. The LSB of the first data byte
contains the input addressed in the query. The other inputs follow toward the
high order end of this byte, and from low order to high order in subsequent
bytes.
Example
: reading 4 DI statuses (starting address is 0000H). Use 6 channels.
Query
Byte1
Byte2
Byte3
Byte4
Byte5
Byte6
Byte7~32
06H
02H
00H
00H
00H
04H
00H
Response
Byte1
Byte2
Byte3
Byte4
Byte5~32
06H
02H
01H
06H
00H
DI status
7
6
5
4
3
2
1
0
0
0
0
0
0
1
1
0
MSB LSB
( DI1 = OFF, DI2=ON, DI3 = ON , DI4 = OFF )