149
b. Read Status of DI (Function Code 02)
Function Code 02
1=On 0=Off
There are 38 DIs in the meter, and the starting address is 0000H.
The following query is to read the 4 DIs Status of address 1 of Acuvim II series
meter.
Query
Transaction
identifier hi
Transaction
identifier lo
Protocol
identifier hi
Protocol
identifier lo
Length hi
Length lo
Unit
identifier
00H
00H
00H
00H
00H
06H
01H
Fun
Data start
reg hi
Data start
reg lo
Data #of regs
hi
Data #of regs
lo
02H
00H
00H
00H
04H
Table 5-7 Read 4 DIs Query Message
Response
The response includes MBAP Header, function code, quantity of data characters
and the data characters.
An example response to read the status of 4 DIs (DI1=On, DI2=On, DI3=On, DI4=
On) is shown as Table 5-8. The status of each is responding to the last 4 bit of the
data.
Shop for Power Metering products online at:
1.877.766.5412
www.
PowerMeterStore
.com
Summary of Contents for Acuvim II
Page 2: ...Shop for Power Metering products online at 1 877 766 5412 www PowerMeterStore com...
Page 8: ...VI Shop for Power Metering products online at 1 877 766 5412 www PowerMeterStore com...
Page 16: ...8 Shop for Power Metering products online at 1 877 766 5412 www PowerMeterStore com...
Page 55: ...47 Shop for Power Metering products online at 1 877 766 5412 www PowerMeterStore com...
Page 60: ...52 Shop for Power Metering products online at 1 877 766 5412 www PowerMeterStore com...
Page 167: ...159 Fig 5 46 Shop for Power Metering products online at 1 877 766 5412 www PowerMeterStore com...
Page 268: ...260 Shop for Power Metering products online at 1 877 766 5412 www PowerMeterStore com...