Zenith ZBTS T-series 100-1200A, I N S TA LL ATI O N A N D O PER ATI N G I N S TR U C TI O N
1
I/O contacts
Switch type: ATS, default settings
Switch type: Bypass, default settings
I01 = ATS Connected
I02 = ATS test
I03 = Bypass Connected
I01 = Bypass Connected
I02 = Bypass Test
I03 = ATS Connected
Ekip Signalling Ekip 2K-1
I11 = Bypass in I
I12 = Bypass in II
O11 = Load connected to S1
(ATS in position I)
O12 = Load connected to S2
(ATS in position II)
I11 = ATS in I
I12 = ATS in II
O11 = Load connected to S1
(Bypass in position I)
O12 = Load connected to S2
(Bypass in position II)
Ekip Signalling Ekip 2K-2
I21 = Bypass in O
I22 = Bypass Test
O21 = ATS in position OI
O22 = ATS in position OII
I21 = ATS in O
I22 = ATS Test
O21 = ATS in position OI
(Bypass in position OI)
O22 = ATS in position OII
(Bypass in position OII)
When moving the switch in / out to a different location (eg. Connected –> Test),
the button of the ATS racking in/out mechanism "PUSH BEFORE OPERATING"
must be pressed, and when the button is pressed, the HMI displays the
information "Racking Enabled". For safety reasons, the switch cannot change
position during a move to different locations.
10 =
Fire fighting input 24 Vdc (+), Rating: SELV
11 = Fire fighting input 24 Vdc (-), Remark: Transfers to O/OFF position, locks
the logic and signals alarm
I3
14 15
12 13
I1
I2
C
I11
I12 O11 O12
I21 I22 O21 O22
10 11
+
-
FIRE
24V
—
Table 6.6 Bypass-Isolation automatic transfer switch:
I/O contacts, default settings, for internal use only
6.1.1 I/O Contacts, Default Settings / Bypass-Isolation Automatic Transfer Switch
These settings are for internal use only, these settings cannot be changed.
Summary of Contents for Zenith ZBTS T Series
Page 2: ...2 Zenith ZBTS T series 100 1200A INSTALL ATION AND OPER ATING INSTRUCTION 1 ...
Page 6: ...6 Zenith ZBTS T series 100 1200A INSTALL ATION AND OPER ATING INSTRUCTION 1 ...
Page 10: ...10 Zenith ZBTS T series 100 1200A INSTALL ATION AND OPER ATING INSTRUCTION 1 ...
Page 44: ...44 Zenith ZBTS T series 100 1200A INSTALL ATION AND OPER ATING INSTRUCTION 1 ...
Page 58: ...58 Zenith ZBTS T series 100 1200A INSTALL ATION AND OPER ATING INSTRUCTION 1 ...
Page 68: ...68 Zenith ZBTS T series 100 1200A INSTALL ATION AND OPER ATING INSTRUCTION 1 ...
Page 100: ...2 100 Zenith ZBTS T series 100 1200A INSTALL ATION AND OPER ATING INSTRUCTION 3 ...
Page 103: ...2 103 34ZBTS _ 30 1200A rev A 1SCC303043M0201 4 ...
Page 105: ...2 105 34ZBTS _ 30 1200A rev A 1SCC303043M0201 4 ...
Page 107: ...2 107 34ZBTS _ 30 1200A rev A 1SCC303043M0201 4 ...
Page 108: ...2 108 Zenith ZBTS T series 100 1200A INSTALL ATION AND OPER ATING INSTRUCTION 4 ...
Page 109: ...2 109 34ZBTS _ 30 1200A rev A 1SCC303043M0201 4 ...