Settings (*Default)
Description
Modules (Optional modules)
Ekip Signalling 2K -3
I 11/12, I 21/22,
I 31/32
Function No Function*
Input disabled
Emergency Stop
Transfers to O position in delayed transition I-O-II type
switches. Disables automatic control mode in both
delayed and open transition types.
Remote Test on Load
Start/stop test on load sequence in rising (NO) or falling
(NC) edge of the input signal.
Remote Test off Load
Start/stop test off load sequence in rising (NO) or falling
(NC) edge of the input signal.
Inhibit ATS
Prevent switch control operations, configuration, test
sequences and generator start in case of priority source
failure.
Manual Retransfer
Disables automatic transfer back to priority source.
Source Priority S1
Sets priority for source 1 in transformer-transformer
application.
Source Priority S2
Sets priority for source 2 in transformer-transformer
application.
Inhibit Transfer
Disables automatic transfer from priority source to non-
priority source.
When input is activated, transfer to non-priority can be
initiated by pressing HMI control button and entering
the device password.
Bypass Running Time
Delays
Bypass any currently running time delay.
Remote Control to S1
Transfer to S1 when active. Overridden by activated
'Remote Control to OFF' signal.
Remote Control to OFF Transfer to position O when active.
Remote Control to S2
Transfer to S2 when active. Overridden by activated
'Remote Control to OFF' or 'Remote Control to S1'
signals.
Reset Alarm
Reset any active switch control alarms (open I failure,
close I failure, open II failure, close II failure).
Inhibit Transfer w/
Override
Prevents ATS to transfer away from acceptable power
source. If connected power source fails ATS can transfer
to another source if it is OK.
Load Shed Input Signal Allows generator to signal to ATS to transfer away from
the generator source to prevent overload. Input works
differently with OXA_ and OXB_ switch types. OXA_
models: ATS transfers to priority source and stays there
while the input is activated. OXB_ models: Transfers
switch to O-position. If priority source restores while
the input is activated ATS will transfer to it.
Manual-Auto Mode
Toggle automatic/HMI control mode, input is active only
in rising/falling edge according to contact type.
Contact
Type
NC
Active open
NO*
Active closed
Continued on the next page
Summary of Contents for Zenith ZBTS T Series
Page 2: ...2 Zenith ZBTS T series 100 1200A INSTALL ATION AND OPER ATING INSTRUCTION 1 ...
Page 6: ...6 Zenith ZBTS T series 100 1200A INSTALL ATION AND OPER ATING INSTRUCTION 1 ...
Page 10: ...10 Zenith ZBTS T series 100 1200A INSTALL ATION AND OPER ATING INSTRUCTION 1 ...
Page 44: ...44 Zenith ZBTS T series 100 1200A INSTALL ATION AND OPER ATING INSTRUCTION 1 ...
Page 58: ...58 Zenith ZBTS T series 100 1200A INSTALL ATION AND OPER ATING INSTRUCTION 1 ...
Page 68: ...68 Zenith ZBTS T series 100 1200A INSTALL ATION AND OPER ATING INSTRUCTION 1 ...
Page 100: ...2 100 Zenith ZBTS T series 100 1200A INSTALL ATION AND OPER ATING INSTRUCTION 3 ...
Page 103: ...2 103 34ZBTS _ 30 1200A rev A 1SCC303043M0201 4 ...
Page 105: ...2 105 34ZBTS _ 30 1200A rev A 1SCC303043M0201 4 ...
Page 107: ...2 107 34ZBTS _ 30 1200A rev A 1SCC303043M0201 4 ...
Page 108: ...2 108 Zenith ZBTS T series 100 1200A INSTALL ATION AND OPER ATING INSTRUCTION 4 ...
Page 109: ...2 109 34ZBTS _ 30 1200A rev A 1SCC303043M0201 4 ...