Zenith ZBTS T-series 100-1200A, I N S TA LL ATI O N A N D O PER ATI N G I N S TR U C TI O N
1
Automatic Transfer Switch, I/O Contacts
Cabling
Rating / Remark
Generator start/stop
Cable size:
(Internal use only *)
0.5…2.5 mm
2
24...14(12) AWG
Stripping length; 6,5 mm, 0,255"
Common, voltage supply
1 5 A@250 Vac (AC-1), 5 A@30 Vdc
Generator start/stop NO
2
Generator start/stop NC
3
Output relay features
Cable size:
0.5…2.5 mm
2
24...14(12) AWG
Common, voltage supply
(Available for customer connections **)
5 5 A@250 Vac (AC-1), 5 A@30 Vdc
Alarm/Product available
6
Programmable output
(default; Alarm/Product
available)
6
Fire Fighting applications
Cable size:
(Internal use only)
0.5…2.5 mm
2
24...14(12) AWG
Only in delayed transition types,
I – O – II or II – O – I
Fire fighting input 24 Vdc (+)
10
SELV
Fire fighting input 24 Vdc (-)
11
Transfers to O/OFF position,
locks the logic and signals alarm
Input contact features
Cable size:
0.5…2.5 mm
2
24...14(12) AWG
Do not connect to any
power supply
Common input
(Internal use only)
12
24 Vdc 5 mA
Programmable input
(default; Emergency stop)
13
Programmable input
(default; Remote test on
load)
14
Programmable input
(default; Remote test off
load)
15
Only in delayed transition,
I – O – II or II – O – I
* See Chapter 7.2.7 Engine/Generator Start Control Connections
** See Chapter 7.2.8 Customer Connections, I/O Signals
6
5
O1
C
10 11
+
-
FIRE
24V
I3
14 15
12 13
I1
I2
C
1
2
3
G
~
1 COMMON
2 CLOSES TO START
3 OPENS TO START
—
Table 6.2 I/O Contacts; cabling In ATS and Bybass. Available for customer connections is only
"Common, Voltage Supply". All other I/O contacts in switches are for internal use only.
See also the table 6.6, Bypass-Isolation Transfer Switch: I/O contacts, default settings
Summary of Contents for Zenith ZBTS T Series
Page 2: ...2 Zenith ZBTS T series 100 1200A INSTALL ATION AND OPER ATING INSTRUCTION 1 ...
Page 6: ...6 Zenith ZBTS T series 100 1200A INSTALL ATION AND OPER ATING INSTRUCTION 1 ...
Page 10: ...10 Zenith ZBTS T series 100 1200A INSTALL ATION AND OPER ATING INSTRUCTION 1 ...
Page 44: ...44 Zenith ZBTS T series 100 1200A INSTALL ATION AND OPER ATING INSTRUCTION 1 ...
Page 58: ...58 Zenith ZBTS T series 100 1200A INSTALL ATION AND OPER ATING INSTRUCTION 1 ...
Page 68: ...68 Zenith ZBTS T series 100 1200A INSTALL ATION AND OPER ATING INSTRUCTION 1 ...
Page 100: ...2 100 Zenith ZBTS T series 100 1200A INSTALL ATION AND OPER ATING INSTRUCTION 3 ...
Page 103: ...2 103 34ZBTS _ 30 1200A rev A 1SCC303043M0201 4 ...
Page 105: ...2 105 34ZBTS _ 30 1200A rev A 1SCC303043M0201 4 ...
Page 107: ...2 107 34ZBTS _ 30 1200A rev A 1SCC303043M0201 4 ...
Page 108: ...2 108 Zenith ZBTS T series 100 1200A INSTALL ATION AND OPER ATING INSTRUCTION 4 ...
Page 109: ...2 109 34ZBTS _ 30 1200A rev A 1SCC303043M0201 4 ...