KNX control elements and application parameters
Application "Internal RTC"
Product manual 2CKA001473B5343
│
260
Notice
This parameter is only available when the "Control function" parameter is set on
"Cooling," "Cooling with additional stage," "Heating and cooling" or "Heating and
cooling with additional stages".
10.24.87 Setpoint settings — Setpoint setting via communication object (DPT 9.001)
Options: No
For comfort, standby, Eco
For comfort, standby, Eco, building protection
This parameter is used to specify whether the setpoint setting is made via communication
objects.
10.24.88 Setpoint settings — Display
Options: Absolute
setpoint
Relative
set value
The display can indicate either the absolute or relative setpoint value.
–
Current setpoint
: On devices with a display, the setpoint is shown as an absolute
temperature, e.g. 21.0°C.
–
Relative setpoint
: On devices with display, the setpoint is indicated as a relative value, e.g. -
5°C to +5°C.
10.24.89 Setpoint settings - Hide temperature unit
Options: Deactivated
Activated
This parameter is used to specify whether the temperature unit is displayed.
10.24.90 Setpoint settings — Send current setpoint
Options:
Cyclic and during change
Only for change
The current setpoint value can be sent to the bus either cyclically and after a change, or only
after a change.
10.24.91 Setpoint settings - Cyclic sending of the current setpoint
Options:
00:05:00 - 18:12:15
This parameter is used to specify the amount of time that will elapse before the current setpoint
is automatically transmitted.