![ABB SmartTouch B/stainless Product Manual Download Page 258](http://html1.mh-extra.com/html/abb/smarttouch-b-stainless/smarttouch-b-stainless_product-manual_3429403258.webp)
KNX control elements and application parameters
Application "Internal RTC"
Product manual 2CKA001473B5343
│
258
Options:
Setting option between 5 - 45
Specifies the comfort temperature for heating economy.
Notice
This parameter is only available when the "Control function" parameter is set
on "Heating", "Heating with additional stage", "Heating and cooling" or
"Heating and cooling with additional stage" and parameter "Setpoint for
standby and Eco are absolute values" is set on "activated".
10.24.79 Setpoint settings — Reduction for heating economy by
Options:
Setting option between 0 - 15
Specifies the temperature in heating mode when nobody is present. On devices with a display,
this mode is indicated by the ECO icon.
Notice
This parameter is only available when the "Control function" parameter is set on
"Heating", "Heating with additional stage", "Heating and cooling" or "Heating and
cooling with additional stages" and parameter "Setpoint for standby and Eco are
absolute values" is set on "deactivated".
10.24.80 Setpoint settings — Setpoint for heating building protection
Options:
Setting option between 5 - 15
Function for protecting the building against the cold. On devices with a display, this mode is
indicated by the frost protection icon. Manual operation is blocked.
Notice
This parameter is only available when the "Control function" parameter is set on
"Heating," "Heating with additional stage," "Heating and cooling" or "Heating and
cooling with additional stages".
10.24.81 Setpoint settings — Setpoint for cooling comfort
Options:
Setting option between 10 - 40
Specifies the comfort temperature for cooling when people are present.
Notice
This parameter is only available when the "Control function" parameter is set on
"Cooling" or "Cooling with additional stage" and parameter "Setpoint heating
comfort = setpoint cooling comfort" is set on "deactivated".
10.24.82 Setpoint settings — Setpoint for cooling standby
Options:
Setting option between 10 - 40
Specifies the comfort temperature for cooling during standby.