KNX control elements and application parameters
Application "Logical functions"
Product manual 2CKA001473B5343
│
221
Options:
Setting options from 0 - 255
See the explanation above.
Telegram delay
:
Options:
Setting option from 200 ms - 10 seconds
The parameter is used to set the time delay for telegrams.
Used outputs
:
Options:
Setting options from 1 - 10
The parameter is used to set the number of output objects to be used in the "Multiplier"
application.
Object type output x
:
Options:
1 bit
1 byte [0 - 100%]
The parameter is used to specify whether the output object consists of a 1-bit value (0/1) or
a 1-byte value (in percent).
Notice
How many "Object type output x" parameters are displayed depends on
the setting of the "Outputs used" parameter.
–
1 bit
: The following parameter appears:
Value of output x
:
Options: 0
1
This parameter is used to specify the value the communication object has on output x.
–
1 byte [0 - 100%]
: The following parameter appears:
Value of output x
:
Options:
Setting options from 0 - 100
This parameter is used to specify the value (in percent) the communication object has
on output x.
Notice
How many "Value of output x" parameters are displayed depends on
the setting of the "Outputs used" parameter.
–
Gate
: This logic function can be used to filter certain signals and block the flow of signals
temporarily. The function has three communication objects: "Control input", "Input" and
"Output". The input or output can take on size 1 bit, 2 bit, 1 byte, 2 byte, 4 byte or 14 byte.
The control can take place from input to output, from output to input and in both directions.
Enabling via the control input can take place via an ON or OFF telegram.
It can also be set as to whether the input signals are to be stored or not "during the blocking
phase". If the setting "Store input signals during blocking" has been selected and if a
telegram has been received on the input during the blocking phase, the output sends its
value.