KNX control elements and application parameters
Control element "Fan switch"
Product manual 2CKA001473B5343
│
150
Options:
<Text for switching level>
The parameter is used to specify the text that is sent for the respective level. The length of
the text is limited to 15 characters.
Note
How many "Text level x" parameters are available depends on the setting
of the "Number of levels" parameter.
Text beyond reach
:
Options:
<Text for "beyond reach">
The parameter is used to specify the text that is displayed when the user-defined texts are
too long. The length of the text is limited to 15 characters.
–
Standard
: Standard texts are displayed for the individual switching levels. The following
supplementary parameter is available:
Text beyond reach
:
Options:
<Text for "beyond reach">
The parameter is used to specify the text that is displayed when the standard texts are too
long. The length of the text is limited to 15 characters.
–
No
: No texts are displayed.
10.8.10 Status control element (icon) is controlled by a separate object
Options: Deactivated
Activated
An additional 1-bit communication object "Status" is enabled via the parameter.
When the object has been enabled, the status display of the control element indicates the
current status of the object. The feedback object can ensure that the correct status is always
displayed.
If an actuator has a separate feedback object, this additional object can check whether the
actuator has switched. For this the feedback object of the actuator must be connected with the
feedback object of the button via a common group address (Action).
If the status display is not activated via a feedback object, the control element always changes
to the other status when actuated.
10.8.11 Enable 1-bit communication object "Disable"
Options: Deactivated
Activated
There is the option of temporarily disabling the function via an additional communication object
"Disable".