KNX control elements and application parameters
Control element "RTC control element"
Product manual 2CKA001473B5343
│
143
10.7
Control element "RTC control element"
10.7.1 Name of the control element
Options: <Name>
Naming of the RTC control element.
The length of the name is limited to 36 characters.
10.7.2 Name of room (otional)
Options: <Name>
Naming a room in which the control element Split Unit Control is located.
The length of the name is limited to 36 characters.
10.7.3 Size of the button
Options: 1x1
1x2
2x2
The parameter is used to specify whether the control element occupies one column (one button
or control frame) or two columns (two buttons or control frames).
10.7.4 Function
icon
Options: <Icon>
Specifies an icon for the function of the button.
10.7.5 Additional
functions/objects
Options: Deactivated
Activated
The parameter is used to specify whether parameter "Delay time during reading of telegrams
after reset [sec.]" is displayed.
10.7.6 Delay time during reading of telegrams after reset [sec.]
Options:
Setting option from 1 - 255 seconds
The parameter is used to specify the number of seconds telegrams are delayed after a reset.
Notice
The parameter can only be set when parameter "Additional functions/objects" is
set on "Yes".