KNX control elements and application parameters
Application "Fault and alarm messages" - Global settings
Product manual 2CKA001473B5343
│
206
10.18
Application "Fault and alarm messages" - Global settings
10.18.1 Use of fault and alarm messages
Options: Deactivated
Activated
The parameter is used to specify whether the fault and alarm messages are displayed.
–
Disabled
: No display in the panel. No additional parameters available.
–
Activated
: The following parameters appear:
10.18.2 Page PIN-protected
Options: Deactivated
Activated
The parameter is used to specify whether the fault and alarm messages application page is
protected by a PIN code.
–
Deactivated
: The application page is not protected.
–
Activated
: The application page can only be called up by entering a PIN code. The following
supplementary parameter is available:
PIN code level
:
Options: Level
1
Level 2
Level
3
The parameter is used to specify the PIN code level for the application page.
Notice
Details about the PIN code, see chapter 9.6.1 “Basic settings (system
settings) of the panel“ on page 77.
10.18.3 Enable export
Options: Deactivated
Activated
The parameter is used to specify whether the messages can be exported under the fixed file
name in CSV format. The messages can then be exported via the application page.
–
Deactivated
: No export. No additional parameters available.
–
Activated
: The following parameter appears:
File name [.CSV]
:
Options: <Text>
The parameter is used to change the file name of the export file.
The length of the name is limited to 60 characters.