KNX control elements and application parameters
Application "Internal RTC"
Product manual 2CKA001473B5343
│
243
configuration.
Note
This parameter is only available when "Control value type" parameter is set
either on "PI continuous, 0 – 100%", "PI PWM, On/Off“ or "Fan coil".
10.24.35 Cooling control - P-component
Options:
Setting option between 1 - 25
The P-component stands for the proportional range in a control. It fluctuates around the setpoint
value and can be used to influence control speed of a PI controller. The smaller the value set,
the faster the control reacts. However, the value should not be set too small because otherwise
there may be a risk of an overshoot. A P-component from 1 to 25 K can be set.
Notice
This parameter is only available when "Control value type" parameter is set
either on "PI continuous, 0 – 100%", "PI PWM, On/Off“ or "Fan coil". In addition,
the "Cooling type" parameter must be set on "Free configuration".
10.24.36 Cooling control - I-component
Options:
Setting option between 0 - 600
The I-component refers to the readjust time of a control. The integral component has the effect
of moving the room temperature slowly toward, and ultimately reaching, the setpoint value.
Depending on the type of system used, the reset time has to have different values. In general,
the more inactive the overall system, the greater the readjust time.
Notice
This parameter is only available when "Control value type" parameter is set
either on "PI continuous, 0 – 100%", "PI PWM, On/Off“ or "Fan coil". In addition,
the "Cooling type" parameter must be set on "Free configuration".
10.24.37 Cooling control - Extended settings
Options: Deactivated
Activated
This parameter enables additional functions, e.g. "Basic stage cooling".