KNX control elements and application parameters
Application "Internal RTC"
Product manual 2CKA001473B5343
│
255
10.24.68 Combined heating and cooling modes — Heating/cooling control value output
Options:
Via 1 object
Via 2 objects
This parameter is used to define whether the control value is transmitted to the climate control
actuator using one or two objects. If the climate control actuator has separate control value
inputs for heating and cooling, or if separate actuators are used, then the option "Via 2 objects"
must be selected. Select the option "Via 1 object" if a single actuator only has one object that
receives both the heating and the cooling control values.
10.24.69 Combined heating and cooling modes — Additional heating/cooling stage control value
output
Options:
Via 1 object
Via 2 objects
This parameter is used to define whether the control value is transmitted to the climate control
actuator using one or two objects. If the climate control actuator has separate control value
inputs for heating and cooling, or if separate actuators are used, then the option "Via 2 objects"
must be selected. Select the option "Via 1 object" if a single actuator only has one object that
receives both the heating and the cooling control values.
Note
This parameter is only available when the "Control function" parameter is set on
"Heating and cooling with additional stages".