KNX control elements and application parameters
Control element "Rocker switch"
Product manual 2CKA001473B5343
│
126
–
Temperature
: After the control element is actuated, the device sends the parameterized
temperature value. The following supplementary parameter is available:
Transmitted value 1 / value 2 [temperature]
:
Options:
Setting option from 16 - 31
–
2-byte value [-32768 - +32767]
: A value is sent as 2-byte value with a sign, e.g. an actuating
value or a time difference. The following supplementary parameter is available:
Sent value 1 / value 2 [-32768 - 32767]
:
Options:
Setting option from -
32768 - +32767
–
2-byte value [0 - 65535]
: A value is sent as 2-byte value without a sign, e.g. an actuating
value or a time interval. The following supplementary parameter is available:
Sent value 1 / value 2 [0 - 65535]
:
Options:
Setting option from 0 - 65535
–
2-byte floating point
: A value is sent as 2-byte floating point value, e.g. a temperature value,
a time duration, a performance or a consumption value. The following supplementary
parameter is available:
Sent value 1 / value 2 [-671088.64 - +670760.96]
:
Options:
Setting option from -671088.64 - +670760.96
–
4-byte value [-2147483648 - 2147483647]
: A value is sent as 4-byte value with a sign, e.g.
an actuating value or a time difference. The following supplementary parameter is available:
Sent value 1 / value 2 [-2147483648 - 2147483647]
:
Options:
Setting option from -2147483648 - 2147483647
–
4-byte value [0 - 4294967295]
: A value is sent as 4-byte value without a sign, e.g. an
actuating value. The following supplementary parameter is available:
Sent value 1 / value 2 [0 - 4294967295]
:
Options:
Setting option from 0 - 4294967295
–
14-byte text
: Makes it possible to send any text. The following supplementary parameter is
available:
Sent value 1 / value 2 [max- 14 characters]
:
Options: <Text>
The length of the text is limited to 14 characters.