ABB | SACE Emax 2
234 | © 2017 ABB | 1SDH001330R0002 - ECN000058721 Rev. A
Electronic accessories | 13 - Ekip Com IEC 61850 modules
Access from the display
With the modules energized, and the Local Bus enabled, the presence of the modules on the terminal box
activates additional menus on the display:
• To set the modules.
• In order to display information on the modules.
To enable the Local Bus, you need to select "On" in the menu
Settings
-
Modules
-
Local Bus
.
The following table shows the path from the display, for setting the function and addressing of the modules:
Settings
…
Main frequency
Modules
Local/Remote
Local Bus
…
Ekip Com IEC 61850
Force Static IP address
SNTP Client Enabled
Static IP Address
Static Network Mask
Static Gateway addr
SNTP Server Address
Ekip Com IEC 61850 *R
(1)
…
Functions
Power Controller
…
(1)
As Ekip Com IEC 61850.
The following table shows the parameters for setting the modules. For further information, see the table on
page 235.
Parameter
Selectable
values
Default
Description
Force Static IP
address
Off, On
Off
• Off = Dynamic IP address.
• On = Static IP address.
SNTP Client
Enabled
Off, On
Off
• Off = Synchronism with the SNTP clock signal
disabled.
• On = Synchronism with the SNTP clock signal enabled.
Static IP
Address
Displayed with static IP Address enabled, it must be selected in order to insert the IP
Address of the modules.
Static Network
Mask
Displayed with static IP Address enabled, it must be selected in order to insert the subnet
mask of the modules.
Static
Gateway addr
Displayed with static IP Address enabled, it must be selected in the presence of
multiple subnets, in order to insert the IP Address of the node to which the modules are
connected.
SNTP Server
Address
Displayed with SNTP client enabled. "On" has to be selected to insert the IP address of
the server with whose SNTP clock signal the modules are to be synchronised.
The following table shows the path from the display for accessing information on the modules:
About
Protection Unit
Circuit-breaker
Modules
…
Ekip Com IEC 61850
Ekip Com IEC 61850 *R
…
Power Controller
Continued on the next page
Summary of Contents for SACE Emax E1.2
Page 2: ...ABB SACE Emax 2 2 2017 ABB 1SDH001330R0002 ECN000058721 Rev A ...
Page 8: ...VI 2017 ABB SACE Emax 2 1SDH001330R0002 ECN000058721 Rev A ...
Page 9: ...ABB SACE Emax 2 3 2017 ABB 1SDH001330R0002 ECN000058721 Rev A ...
Page 310: ...ABB SACE Emax 2 304 2017 ABB 1SDH001330R0002 ECN000058721 Rev A Service 1 Power Care ...