ABB | SACE Emax 2
Ekip Touch protection trip unit | 15 - Touch measurements
105 | © 2017 ABB | 1SDH001330R0002 - ECN000058721 Rev. A
15 - Touch measurements
Presentation
Touch measurements are available in all the models of trip units of the Ekip Touch range.
The following is a list of the available measurements:
Measurements
Description
Instantaneous currents
Real Time measurements of the currents
Trip
List of the trip for basic protections
Events
List of events, changes of state, alarms recorded by the trip unit
Maximum current
History of the maximum currents recorded with an interval that can be set
Minimum current
History of the minimum currents recorded with an interval that can be set
Peak factor
Real time measurement of the peak factor of the currents
Contact Wear
Calculation of the wear of the contacts
Datalogger
Recording of the waveform of the currents and the digital states
Operation counters
Number of mechanical and electrical operations
Instantaneous currents
Description
Instantaneous currents are real time measurements of earth fault and phase currents, expressed as r.m.s.
value.
Representations and access pages
The current measurements are available in different forms, accessible from the following pages:
•
Histograms
page: graphical representation in the form of a histogram of the phase currents, and
measurement in Amperes of the highest current.
•
Measuring instruments
page: graphical representation in the form of an ammeter and measurement in
Amperes of the highest current.
•
Measurements
page: measurements in Amperes of all the phase currents and earth fault current.
NOTE:
•
The measurement of the earth fault current is available only with LSIG versions of trip units.
•
The measurements in Amperes are available from a minimum value of 0.03 In for the phase
currents, and 0.08 In the for earth fault current. For lower currents “…” is displayed.
• In the
Histograms
page, the graphical representation of the currents is in relation to 1 In, with
a maximum value of 1.25 In
Tripping
Path
Main page - Menu - Measurements - Historicals
Description
The trip unit is able to record the last 30 openings of the circuit-breaker caused by protection trips (trips).
The trips are associated to the following information:
• The protection that tripped.
• The progressive number.
• The date and time of the opening (referring to the internal clock)
• The measurements associated to the trip protection.
NOTE:
•
Each trip is associated to a progressive number that is increased with every trip.
•
If the trip unit has exceeded the threshold of the 30 openings, the oldest ones are progressively
overwritten.
Continued on the next page
Summary of Contents for SACE Emax E1.2
Page 2: ...ABB SACE Emax 2 2 2017 ABB 1SDH001330R0002 ECN000058721 Rev A ...
Page 8: ...VI 2017 ABB SACE Emax 2 1SDH001330R0002 ECN000058721 Rev A ...
Page 9: ...ABB SACE Emax 2 3 2017 ABB 1SDH001330R0002 ECN000058721 Rev A ...
Page 310: ...ABB SACE Emax 2 304 2017 ABB 1SDH001330R0002 ECN000058721 Rev A Service 1 Power Care ...