ABB | SACE Emax 2
Ekip Touch protection trip unit | 1 - Layout of the interface
37 | © 2017 ABB | 1SDH001330R0002 - ECN000058721 Rev. A
Ekip Touch protection trip unit
1 - Layout of the interface
Functions of the interface
The operator interface for Ekip Touch trip units allows to:
• Dislpay signals and measurements related to the functions in progress, or recorded events.
• Configure the circuit-breaker, and the installation parameters.
• Set the parameters for available protections and for other functions of the trip unit.
• Set parameters for the connected accessory modules.
• Perform tests.
• Display information on the circuit-breaker, trip unit, and connected accessory modules.
Components of the interface
The operator interface for the Ekip Touch trip units appears as follows:
L1
U12
528.9A
95.3V
U12
U31
L1
L2
L3
U23
Ne
03:55
A
B
C
D
E
F
G
Figure 4
The following table provides a description of the parts of the interface:
Pos. Description
A
Touchscreen display.
B
Power LED, green.
C
LED Warning, yellow.
D
LED Alarm, red.
E
HOME
key opens the main page, or the
start page
.
F
iTEST
key. If the main page or a level 2 page is displayed (see below), whenever you press on it
the following pages are displayed in succession:
•
List of Alarms
, if there are any messages.
•
Protection unit
, with information on Mainboard and trip unit.
•
Circuit-breaker
, with information on the circuit-breaker.
•
Last opening
, with information on the last opening.
If the
Trip Test
item has been selected in the
Test
menu, it will execute the opening command
when pressed and held for at least 7 seconds.
G
Test connector.
Summary of Contents for SACE Emax E1.2
Page 2: ...ABB SACE Emax 2 2 2017 ABB 1SDH001330R0002 ECN000058721 Rev A ...
Page 8: ...VI 2017 ABB SACE Emax 2 1SDH001330R0002 ECN000058721 Rev A ...
Page 9: ...ABB SACE Emax 2 3 2017 ABB 1SDH001330R0002 ECN000058721 Rev A ...
Page 310: ...ABB SACE Emax 2 304 2017 ABB 1SDH001330R0002 ECN000058721 Rev A Service 1 Power Care ...