ABB | SACE Emax 2
44 | © 2017 ABB | 1SDH001330R0002 - ECN000058721 Rev. A
Ekip Touch protection trip unit | 4 - Measuring instruments pages
4 - Measuring instruments pages
Description
The
Measuring instruments
pages show an indicator of the maximum phase current, or the maximum line-
to-line voltage, or the active, reactive or apparent power.
The page orientation (horizontal by default) can be changed from the
Settings
menu, by selecting
System
-
View
(see the chapter "6 - Menu", and the paragraph "Settings Menu" on page 49).
Components of the pages
The pages appear as follows:
L3
A
B
D
. . . .
A
528.9 A
C
. . . .
Figure 9
The following table provides a description of the various areas of the pages:
Pos.
Description
A
Type of indicator:
• A: ammeter, with measurement of the maximum phase current.
• V: ammeter, with measurement of the maximum phase-to-phase voltage.
• kW: measurement of the active power.
• kVAR: measurement of the reactive power.
• kVA: measurement of the apparent power.
NOTE
:
all the indicators except the ammeter are available with the Ekip Measuring
module.
B
Measurement expressed as a percentage of the nominal value set.
C
Measurement as an absolute value (A, V, kW, kVA).
D
Phase current or phase-to-phase voltage, to which the measurement refers.
E
Diagnosis bar.
Possible operations
In these pages, the following operations are possible:
• By touching the sides of the display, scroll through the available indicators.
• Open the page
Alarm List
.
Summary of Contents for SACE Emax E1.2
Page 2: ...ABB SACE Emax 2 2 2017 ABB 1SDH001330R0002 ECN000058721 Rev A ...
Page 8: ...VI 2017 ABB SACE Emax 2 1SDH001330R0002 ECN000058721 Rev A ...
Page 9: ...ABB SACE Emax 2 3 2017 ABB 1SDH001330R0002 ECN000058721 Rev A ...
Page 310: ...ABB SACE Emax 2 304 2017 ABB 1SDH001330R0002 ECN000058721 Rev A Service 1 Power Care ...