ABB | SACE Emax 2
196 | © 2017 ABB | 1SDH001330R0002 - ECN000058721 Rev. A
Electronic accessories | 5 - Ekip Signalling 4K module
Continued from the previous page
The following table shows the configuration parameters of the outputs:
Parameter
Selectable values
Default
Description
Signal source
• None
• Prealarm L
• Delay L
• Delay S
• Opening L
• Opening S
• Opening G
• Opening I
• Every opening
• Every delay
• Threshold1 I1
(1)
• Threshold2 I1
(1)
• CB Open
• CB Close
• Local Bus Not Active
• Custom
(2)
None
The event that activates the outputs, so as to make
the contact:
• Closed, if set as NO.
• Open, if set as NC.
Delay
0.00…100.00 s
steps of 0.01 s
0.00 s
Standby time after the selected event has occurred,
and before the output is activated (if the event
disappears before a time equal to the delay elapsed,
the output is not activated). If 0.00 s is selected, the
value 300
μ
s is assigned to the parameter.
Contact type NO, NC
NO
• NO = Contact normally open.
• NC = Contact normally closed.
Self-latching Off, On
Off
• Off = The output is deactivated when the event
disappears.
• On = When the event disappears, the output is
kept active for the minimum time selected.
IMPORTANT: if the output is used for the
Power Controller function, self-latching
must not be enabled.
Min activation
time
0 ms, 100 ms, 200 ms,
Power Controller
0 ms
The "Power Controller" value can be selected only if
the output is used for the Power Controller function
(see the chapter "23 - Ekip Power Controller", on
page 131). Then the output is kept active for a fixed
time associated with the function, regardless of the
persistence of the event that activated it.
On the contrary, with self-latching enabled, the
minimum time in which the output is kept active (once
the selected time has elapsed, the output is kept
active as long as the event that activated it persists).
IMPORTANT: if the output is not used for
the Power Controller function, the “Power
Controller” value must not be selected.
(1)
For the sources Threshold1 I1 and Threshold2 I1, see the chapter "9 - Touch protections", and the
paragraph "Current thresholds”, on page 69.
(2)
The Custom source is a combination of default events that can be modified using the Ekip Connect software
so as to make the closing/opening of the contact correspond to a wide range of combinations of the status
bits of the trip unit.
Continued on the next page
Summary of Contents for SACE Emax E1.2
Page 2: ...ABB SACE Emax 2 2 2017 ABB 1SDH001330R0002 ECN000058721 Rev A ...
Page 8: ...VI 2017 ABB SACE Emax 2 1SDH001330R0002 ECN000058721 Rev A ...
Page 9: ...ABB SACE Emax 2 3 2017 ABB 1SDH001330R0002 ECN000058721 Rev A ...
Page 310: ...ABB SACE Emax 2 304 2017 ABB 1SDH001330R0002 ECN000058721 Rev A Service 1 Power Care ...