ABB | SACE Emax 2
Mechanical accessories | 7 - Installation
289 | © 2017 ABB | 1SDH001330R0002 - ECN000058721 Rev. A
Continued from the previous page
To optimize the thermal efficiency, it is recommended to adhere to the following installation
guidelines:
• Guarantee the maximum possible distance between the input and output busbars. See the example
• Guarantee the maximum use of the surface of the terminal. See the example Figure 101.
• Make sure that the distance between the holes and the end of the terminal and between the holes and
extremity of the busbar is the same. See the example Figure 102.
• Make sure that, accordingly to the number of busbars and terminal tangs, the busbars of the lateral phases
are as distant as possible from the busbars of the central phase. See the example Figure 103.
OK
NO
Figure 100
OK
NO
Figure 101
OK
= =
NO
≠ ≠
Figure 102
OK
NO
OK
NO
Figure 103