Fault tracing
81
Fault tracing
LED indications
The RETA-01 module is equipped with three diagnostic LEDs. The
description of the LEDs is below.
Name Colour Function
Link/Activity
Green
Flashing green
- Module is receiving/transmitting
on Ethernet
Steady green
- Module has detected link
Off
- Module cannot detect link
Network S
tatus
Red/
Green
Flashing red
-
EtherNet/IP:
One or more
connections timed out;
Modbus/TCP:
No message
has been received within configured time
Steady red
- Duplicate IP address
Flashing green
- Waiting for connections
Steady green
-
EtherNet/IP:
At least one
EtherNet/IP connection is open against the
module (even to the Message router);
Modbus/
TCP:
At least one Modbus/TCP connection is
open against the module
M
odule S
tatus
Red/
Green
Flashing red
- Minor fault (e.g. communication
with application lost but recoverable)
Steady red
- Major fault (e.g. bad flash, failed
memory test, non-recoverable communication
problem with host)
Steady green
- Normal operation
Network Status
(not used)
Link/Activity
Module Status
Summary of Contents for RETA-01
Page 1: ...ABB Drives User s Manual Ethernet Adapter Module RETA 01 ...
Page 2: ......
Page 4: ......
Page 6: ...Safety instructions 6 ...
Page 10: ...Table of Contents 10 ...
Page 14: ...Introduction 14 ...
Page 28: ...Quick start up guide 28 ...
Page 30: ...Mechanical installation 30 ...
Page 32: ...Electrical installation 32 ...
Page 40: ...Drive configuration 40 ...
Page 80: ...Communication 80 ...
Page 82: ...Fault tracing 82 ...
Page 85: ......