Network configuration
43
DHCP/BOOTP Automatically receive the configuration from
a DHCP server.
A DHCP server
is required on
the network.
Settings stored
in RETA-01
configuration
parameters
Use the configuration stored in the RETA-01
configuration parameters. See Table
in the
chapter
RETA-01 must
be restarted or
parameters
refreshed
(RETA-01
configuration
parameter 27
'REFRESH') for
any configuration
changes to take
effect.
Gleaning
(ARP)
Change the IP address from a PC using the
following commands:
arp -s <IP address> <MAC address>
ping <IP address>
arp -d <IP address>
The
arp -s
command will store the IP and
MAC addresses in the PC ARP table. When
the
ping
command is executed, the PC will
send the message to the module using the
MAC address. The module changes its IP
address to the given one.
The MAC
address of the
module can be
found on a label
on the RETA-01
module.
Method
Description
Note
Summary of Contents for RETA-01