Communication
72
Instance 0x01, Attributes
2)
Supported only with assembly instance 21
ID#
Attribute name Services Description
Data type
0x03 At Reference
Get
Frequency arrival
BOOL
0x04 NetRef
2)
Get/Set
Requests torque or speed reference
to be local or from the network.
0 = Set Reference not net Control 1
= Set Reference at net Control Note
that the actual status of torque or
speed reference is reflected in
attribute RefFromNet 0x1D (29).
BOOL
0x06 Drive Mode
Get
0 = Vendor specific
UINT8
0x07 Speed Actual
Get
Units RPM/2
SpeedScale
SINT16
0x08 SpeedRef
Get/Set
Units RPM/2
SpeedScale
SINT16
0x09 Current Actual
Get
Units 100 msec/2
CurrentScale
UINT16
0x0A Power Actual
Get
Units Watts/2
PowerScale
UINT18
0x0B Torque Actual
Get
Units Nm/2
TorqueScale
UINT16
0x12 AccelTime
Get/Set
Units msec/2
TimeScale
UINT16
0x13 DecelTime
Get/Set
Units msec/2
TimeScale
UINT16
0x14 Low speed limit Get/Set
Units RPM/2
SpeedScale
UINT16
0x15 High speed limit Get/Set
Units RPM/2
SpeedScale
UINT16
0x16 Speed Scale
Get/Set
Speed scaling factor
UINT8
0x17 Current Scale
Get/Set
Current scaling factor
UINT8
0x18 Torque Scale
Get/Set
Torque scaling factor
UINT8
0x1A Power Scale
Get/Set
Power scaling factor
UINT8
0x1B Voltage Scale
Get/Set
Voltage scaling factor
UINT8
0x1C Time Scale
Get/Set
Time scaling factor
UINT8
0x1D Ref From Net
Get
BOOL
0x1F Field I or IV
Get/Set
Always to be set to 0
-
Summary of Contents for RETA-01
Page 1: ...ABB Drives User s Manual Ethernet Adapter Module RETA 01 ...
Page 2: ......
Page 4: ......
Page 6: ...Safety instructions 6 ...
Page 10: ...Table of Contents 10 ...
Page 14: ...Introduction 14 ...
Page 28: ...Quick start up guide 28 ...
Page 30: ...Mechanical installation 30 ...
Page 32: ...Electrical installation 32 ...
Page 40: ...Drive configuration 40 ...
Page 80: ...Communication 80 ...
Page 82: ...Fault tracing 82 ...
Page 85: ......