Drive configuration
37
16 Protocol
Selects the application protocol and communication profile for the
network communication.
17 Modbus timeout
The Modbus protocol has no implementation for time-out on
application layer and this may be required when controlling a
drive. A supervision method has been implemented for this
purpose. If Modbus timeout is set to zero, this feature is disabled.
The unit of the parameter is 100 milliseconds (e.g. ‘22’ will give a
timeout of 2.2 seconds).
If the communication fault function of the drive is activated,
Modbus timeout is the sum of communication fault time and the
time defined here.
18 Stop function
Defines the motor stopping method.
Note:
This parameter is only effective if the EtherNet/IP network
protocol is selected at parameter
.
19 Output 1
20 Output 2
21 Output 3
22 Output 4
When Modbus/TCP protocol is in use, these parameters define
the output data words or drive parameters that are updated
cyclically between the drive and RETA-01. For the user this can be
seen as faster response for the Modbus queries.
0 = Modbus/TCP
1 = EtherNet/IP AC/DC communication profile
2 = EtherNet/IP ABB Drives communication profile
0 = Ramp stop
1 = Coast stop
Summary of Contents for RETA-01
Page 1: ...ABB Drives User s Manual Ethernet Adapter Module RETA 01 ...
Page 2: ......
Page 4: ......
Page 6: ...Safety instructions 6 ...
Page 10: ...Table of Contents 10 ...
Page 14: ...Introduction 14 ...
Page 28: ...Quick start up guide 28 ...
Page 30: ...Mechanical installation 30 ...
Page 32: ...Electrical installation 32 ...
Page 40: ...Drive configuration 40 ...
Page 80: ...Communication 80 ...
Page 82: ...Fault tracing 82 ...
Page 85: ......