Quick start-up guide
27
Table 7. Drive configuration for User Specific Control
Drive parameter
Example setting for ACS550
10.01 EXT1 COMMANDS
COMM
10.03 DIRECTION
REQUEST
11.03 REF1 SELECT
COMM
16.04 FAULT RESET SEL
COMM
98.02 COMM PROT SEL
EXT FBA
51.01 MODULE TYPE
ETHERNET
51.02 COMM RATE
0 (Auto-negotiation)
51.03 DHCP
1 (Enabled)
51.04 - 51.07 IP ADDRESS
10.0.0.6
51.08 - 51.11 SUBNET MASK
255.255.255.0
51.12 - 51.15 GW ADDRESS
0.0.0.0
51.16 PROTOCOL
2 (ABB Drives profile)
51.19 OUTPUT 1
1 (Command word)
51.20 OUTPUT 2
2 (Reference 1)
51.23 INPUT 1
4 (Status word)
51.24 INPUT 2
5 (Actual value 1)
51.25 INPUT 3
104 (Par. 1.04 CURRENT)