Network configuration
42
Method
Description
Note
DIP switch (S1) By default, the IP address is defined by
)
.
Setting any DIP actuator to ON enables
hardware selection. DIP actuators 1 to 8
define the last octet (1 to 254) of the IP
address in binary. Actuator 8 represents the
least significant bit.
Only read at
start-up.
Only for intranet
use.
IP address:
192.168.0.
xxx
Subnet mask:
255.255.255.0
Gateway:
0.0.0.0
where
xxx
stands for a value between 1 and
254 and is selected by DIP switch S1.
Example DIP settings:
Intranet IP
address
S1 actuator
positions
(Selected by
software)
OFF oooooooo
ON
12345678
192.168.0.1
OFF ooooooo
ON o
12345678
192.168.0.2
OFF oooooo o
ON o
12345678
• • •
• • •
192.168.0.255
OFF
ON oooooooo
12345678